Free browser-based tools for transformer dissolved gas analysis. The diagnostic calculator runs the standard ratio and zone rules. The Modbus decoder converts raw registers from DGA monitors and PLCs. The live dashboard shows how continuous DGA data is displayed and alarmed.

How the tools fit together

The diagnostic calculator is the interpretation step. You enter a laboratory or online DGA result, and the page applies Duval Triangle 1, the IEC 60599 basic gas ratios, the Rogers four-ratio codes and the IEEE C57.104-2019 Table 1 comparison to the same gas set. Each method uses a different number of gases, so the page states which inputs are active instead of silently ignoring the rest. The output includes the fault zone, the matching ratio row, the Rogers code and the IEEE status candidate, with the source of every value labelled as entered, preset or read from a shared link.

The Modbus decoder covers the data-acquisition step. A DGA monitor reports holding registers, and the same four bytes can be interpreted as ABCD, BADC, CDAB or DCBA. The decoder shows every interpretation side by side so you can match the register map in the device manual. The dashboard demo covers the presentation step: how 1 Hz readings, alarm thresholds and trend charts behave in a live monitoring interface. None of these tools replaces a laboratory oil test. They shorten the path from raw numbers to a defensible first diagnosis.

Scope. These tools apply published diagnostic rules and are intended for engineering reference and training. They do not replace a laboratory oil test or a qualified engineer’s judgement. The live dashboard uses simulated data and is not connected to any monitor.