PAS DGA offers four distinct dissolved gas analysis solutions — from an OEM-grade hydrogen sensor probe to a full laboratory-grade multi-gas monitor. All built on proprietary palladium-nickel (Pd-Ni) alloy thin-film sensor technology. Use this guide to find the right monitor for your transformer application.

Find your monitor in three questions. Pick the application, add the system voltage, and say what you need the data for. The tool returns the model this page’s selection table points to first, plus the trade-off worth weighing. It states no figures of its own — open the model page for the specification.

3. What do you need the data for?

Pick an application above and the tool returns the model this page’s selection table points to, with the trade-off to weigh. Not sure which application you have? Use the model links below, or send us the nameplate.

Key figures at a glance

  • Multi-gas monitors measure on a cycle of 1 to 24 hours (default 4 hours) — up to 6 measurements per day with no operator involvement.
  • Palladium-alloy hydrogen sensors hold ±15% of reading or ±5 ppm accuracy with no routine calibration.
  • The laser photoacoustic (LPAS) detection cell has no consumables and its laser diode is rated for more than 50,000 hours of continuous operation.

Product Family Overview

Model Type Gases Detection Best For
DGA-300 OEM Sensor Probe H₂ 2 ppm System integrators, custom monitoring platforms, OEM partners
DGA-500 Standard Online Monitor H₂ 5 ppm Cost-sensitive deployments, distribution transformers, fleet rollouts
DGA-200 Advanced Online Monitor H₂ + Multi-Gas (optional) 5 ppm H₂ Remote substations, SCADA integration, multi-gas capable
DGM-900 Multi-Gas Online Monitor 7 fault gases + moisture Sub-ppm (LPAS) Large power transformers, critical assets, full DGA diagnostics

How to Choose a DGA Monitor: Four Decisions

Most of the specification work is settled before anyone compares models. Four questions account for nearly all of it, and taking them in this order avoids buying either more instrument than the asset needs or less than the fault type you have to diagnose.

1. Hydrogen trend, or multi-gas diagnosis?

A hydrogen sensor answers one question: is something developing? It measures the earliest and most universal fault gas, costs a fraction of a multi-gas analyser and needs no consumables, which is why it is the default for fleets. What it cannot do is name the fault. If the output has to say whether the fault is thermal or electrical, you need the hydrocarbon gases — CH₄, C₂H₄, C₂H₂, C₂H₆ — because every ratio method (Rogers, Doernenburg, IEC 60599) and both Duval polygons are built on them. The hydrogen-only versus multi-gas trade-off is worth settling first, because it decides the price bracket everything else is compared in.

2. Which asset class is the monitor for?

Distribution transformers are numerous and individually low-value: the deciding figure is cost per monitoring point, and a hydrogen monitor on every unit is usually the only arithmetic that works. Generator step-up units, HVDC converter transformers and large power transformers are the opposite — few units, high consequence, and a fault that cannot be typed is a fault that cannot be acted on. That is where sub-ppm multi-gas measurement with moisture earns its price. A single fleet can legitimately need both, and the selection table below reflects that rather than pushing one model across the board.

3. Where does the data go?

A monitor that raises a local alarm and a monitor that feeds SCADA are different purchases. If readings are going into an existing condition-monitoring platform, confirm the protocol and register map before selection, not after delivery. If there is no platform, the unit’s own dashboard and alarm logic matter more than an extra gas channel. The online versus offline decision belongs here too: a permanent installation and a periodic sampling programme solve different problems.

4. Finished monitor, or sensing element?

If you build monitoring systems, the right unit is the sensor probe, not the monitor — you supply the enclosure, the datalogger and the analytics. Buying a finished monitor to cannibalise it is an expensive way to obtain a sensor, and it puts someone else’s firmware inside your product.

The comparison below applies these four decisions to the four PAS DGA models. Where two models both fit, the trade-off is stated rather than hidden: the cheaper unit wins unless you need fault typing or sub-ppm detection, and the more capable unit is wasted on an asset that only needs a trend.

Quick Selection by Application

Application Voltage Recommended Why
Distribution Transformer < 69 kV DGA-500 Cost-effective H₂ monitoring, zero maintenance, 10-year sensor life
Power Transformer 69–230 kV DGA-200 H₂ + optional multi-gas upgrade path
Large Power Transformer 230–500 kV DGM-900 Full 7-gas + moisture, laser PAS sub-ppm detection
Generator Step-Up Any DGM-900 or DGA-200 Multi-gas for comprehensive fault coverage; H₂ for budget-conscious
HVDC Converter Transformer ±500 kV+ DGM-900 Sub-ppm multi-gas with photoacoustic spectroscopy, full Duval Triangle diagnostics
Industrial / Arc Furnace < 69 kV DGA-500 Rugged IP65 cast aluminum, vibration-resistant, -40 to +85°C
Offshore / Marine Any DGA-200 or DGM-900 No cabling required, salt-fog resistant
OEM / System Integration N/A DGA-300 Compact probe form factor, 4–20 mA + RS-485, <10 μA standby
Railway Traction 25 kV DGA-500 Compact, vibration-resistant, <60s response time

Detailed Feature Comparison

Feature DGA-300 DGA-500 DGA-200 DGM-900
Product Type OEM Probe Standard Monitor Advanced Monitor Multi-Gas Monitor
Gases Detected H₂ H₂ H₂ + optional: CO, CH₄, C₂H₂, C₂H₄ 7 gases + Moisture
Detection Limit 2 ppm 5 ppm Not specified Sub-ppm (LPAS)
Sensor Technology Pd Alloy MOSFET Pd Alloy Thin-Film Pd Alloy Thin-Film Multi-Channel LPAS
Response Time < 10 min < 30 min Not specified <120 s (full cycle)
Communication 4–20 mA, RS-485 MODBUS MODBUS, 4–20 mA MODBUS RTU, 4–20 mA MODBUS RTU
Enclosure Rating IP67 (probe) IP67 IP66 IP65
Operating Temp 0 ~ 60 ℃ −40 ~ 105 ℃ −40 ~ 105 ℃ -40 to +70°C
Sensor Life10 Years10 Years10 Years10 Years
Key Advantage 2 ppm limit of detection in an OEM probe Standalone monitor mounted at the transformer valve H₂ plus an optional multi-gas upgrade path Lab-grade multi-gas spectroscopy in an online monitor

Sensor Technology: Why Palladium Thin-Film?

All PAS DGA monitors use palladium (Pd) alloy thin-film sensors fabricated with MEMS processes. Unlike electrochemical sensors that degrade or gas chromatography that requires consumables, our solid-state technology delivers:

  • Zero consumables — no carrier gas, no calibration gas, no columns
  • 10-year expected sensor life — no electrolyte depletion, no mechanical wear
  • Hydrogen-specific — Pd alloy selectively absorbs only H₂ molecules
  • Instant-on — no warm-up period, <60 seconds to first reading

Learn more: Palladium Thin-Film Technology Deep-Dive | Hydrogen Sensor Product Family

Need Help Deciding?

Our application engineers will recommend the right DGA solution based on your transformer specifications, operating conditions, and budget. Typical response time: same business day.

Request a Recommendation →
  Contact Technical Support

Also Available

Category Products Link
Hydrogen Sensors Full Pd thin-film sensor portfolio — DGA-300, DGA-500, DGA-200 H₂ module View Hydrogen Sensors
Accessories & Software Mounting kits, communication modules, calibration tools, spare parts, PAS Dashboard software View Accessories
All Products Complete DGA product catalog with detailed specifications View All Products

Not Sure Which Monitor Fits Your Application?

Send us your transformer specifications and operating conditions. Our application engineers will recommend the optimal DGA solution — same business day response.

General Contact Form

FAQ

Q: What gases does a DGA monitor detect?

A: The DGM-900 detects 7 fault gases plus moisture: hydrogen (H₂), carbon monoxide (CO), carbon dioxide (CO₂), methane (CH₄), ethane (C₂H₆), ethylene (C₂H₄) and acetylene (C₂H₂), plus moisture (H₂O). The DGA-200/300/500 hydrogen sensors detect H₂ down to 2 ppm.

Q: What communication protocols are supported?

A: MODBUS RTU (RS-485) digital output and 4–20 mA analog output, with programmable dry-contact relay alarms. The exact interface set differs by model — see the product page or datasheet for the interfaces supplied with each unit.