STANDALONE SENSOR

Overview

A dissolved-hydrogen sensor that mounts independently on the transformer body, installed directly at the transformer ball valve and suitable for outdoor service. IP67 protection together with an applicable oil temperature of −40 ~ 105 ℃ allows long-term operation in outdoor transformer environments. The chip uses a palladium alloy thin-film resistor structure with a mature, stable Pd-alloy doping system, giving excellent long-term stability and freedom from periodic maintenance. In addition to dissolved hydrogen and oil temperature, the DGA-500 can be supplied with an optional moisture sensor and an optional oil pressure sensor.

5 ~ 5000 ppm
H₂ Range
5 ppm
Detection Limit
IP67
Ingress Protection
≤ 500 g
Weight
PAS DGA DGA-500 standalone dissolved hydrogen sensor for transformers

Mounts directly at the transformer ball valve — IP67, −40 ~ 105 ℃ applicable oil temperature

Key Features

🔬

Solid-State Palladium Alloy Thin-Film

The chip uses a palladium alloy thin-film resistor structure with a mature, stable Pd-alloy doping system and specific composite thin-film fabrication, giving excellent long-term stability and sensitivity with no oil-gas separation.

🎯

Hydrogen-Specific Coating

A specific coating lets the sensor work reliably in backgrounds containing CO and CH compounds, so detection accuracy is not affected by other gases.

Hydrogen Detection in Different Backgrounds

Supports on-line hydrogen monitoring in mixed-gas backgrounds such as N₂, pure O₂ and inert gases.

🌡️

Self-Regulating Working Temperature

A thin-film temperature sensor is integrated on the chip, allowing the working temperature to be adjusted automatically — no external temperature or flow-control devices are required.

💧

Optional Moisture and Oil Pressure

Add a moisture sensor (0 ~ 100 %RS) and an oil pressure sensor (0 ~ 1 MPa) to the dissolved hydrogen and oil temperature measurement.

🛡️

IP67, Outdoor Capable

IP67 protection with a −40 ~ 105 ℃ applicable oil temperature for long-term outdoor service. A corrosion-proof enclosure is available as an option for harsher site conditions.

🔌

Digital and 4 ~ 20 mA Analog Outputs

RS-485 with Modbus_RTU for configuration and data, plus an isolated 4 ~ 20 mA analog output whose span is configurable to the reporting range — so the DGA-500 can drive a SCADA or PLC analog input directly.

Technical Specifications

Dissolved Hydrogen

Detection Principle Palladium alloy thin film
Measuring Range 5 ~ 5000 ppm
Limit of Detection 5 ppm
Accuracy ±15% reading or ±5 ppm (whichever is greater)
Repeatability ±5% reading or ±5 ppm (whichever is greater)
Resolution 1 ppm
Applicable Oil Temperature −40 ~ 105 ℃
Response Time τ90 < 30 min (oil concentration above 100 ppm)

Moisture (optional)

Measuring Range 0 ~ 100 %RS
Accuracy at 20 ℃ 0 ~ 90 %RS: ±2 %RS
90 ~ 100 %RS: ±3 %RS
Response Time τ90 < 10 min

Oil Temperature

Measuring Range −40 ~ 120 ℃
Accuracy at 20 ℃ ±1 ℃

Oil Pressure (optional)

Measuring Range 0 ~ 1 MPa
Accuracy ±1 % F.S.
Resolution 0.1 kPa
Overload Capacity 3 MPa

Electrical & Other

Power Supply 24 V DC ±10%, 0.3 A (max)
Digital Output RS-485
Communication Protocol Modbus_RTU
Analog Output Isolated 4 ~ 20 mA, span configurable (fault 3.5 mA, not-ready 2.0 mA)
Ingress Protection IP67
Data Storage Default interval 30 s (adjustable), 74,604 entries
Expected Life 10 years
Weight ≤ 500 g

Type Configurations

DGA-500 Base Dissolved hydrogen and oil temperature sensor
DGA-500 with moisture Plus moisture sensor
DGA-500 with moisture and oil pressure Plus moisture and oil pressure sensors
Corrosion-proof enclosure Optional, for DGA-500

Outline Dimensions

Body Length 226 mm
Probe Rod Length 110 mm
Overall Length 241.5 mm
Probe Rod Diameter φ12.7 mm
Probe Root to Fitting ≤ 45 mm
Process Connection 1/2 in. two-ferrule tube fittings

Range Limit

Range limit: the DGA-500 may only be used for hydrogen measurement in oil below 5000 ppm. Exceeding this range may cause the sensor chip to drift or even fail. Operation beyond the measuring range may cause irreversible damage to the sensor probe. A corrosion-proof enclosure is available as an option for this product.

Calibration follows the product manual: save the current state with the DA command, take an oil sample near the probe for off-line DGA analysis per ASTM D3612, and if the deviation exceeds 15% calibrate to the actual value with the DB command. The DX command clears the calibration data and returns the unit to factory calibration. Oil temperature, pressure and moisture calibration is performed with the CT command over RS-232 or via the MODBUS_RTU protocol.

Model Comparison

Feature DGA-300 (OEM) DGA-500 (Standalone) DGA-200 (Integrated) DGM-900 (Multi-Gas)
H₂ Range 2 ~ 2000 ppm 5 ~ 5000 ppm 5 ~ 5000 ppm —
H₂ Detection Limit 2 ppm 5 ppm Not specified —
H₂ Accuracy ±20% or ±2 ppm ±15% or ±5 ppm ±15% or ±5 ppm —
Applicable Oil Temperature 0 ~ 60 ℃ −40 ~ 105 ℃ −40 ~ 105 ℃ —
Multi-Gas — — — 7 gases + moisture
O₂ / N₂ optional
Sensor Technology Pd alloy MOSFET thin film Pd alloy thin-film resistor Palladium alloy thin film Pd Thin-Film + LPAS
MODBUS ✓ ✓ ✓ ✓
IEC 61850 — — — ✓
Rating IP67 IP67 IP66 —
Weight ≤ 350 g ≤ 500 g approx. 1.75 kg —
Best For OEM Integration Standalone Transformer Mounting Distribution Transformer Fleets Critical Asset Protection

The DGM-900 column repeats the figures already published on the DGM-900 product page and was not revised here; “—” marks a row not compared on this page. See the DGM-900 product page for its full specification.

Modbus Interface — Data Available to Your Host

DGA-300 and DGA-500 are standard hardware half-duplex Modbus RTU slaves. Default 19200 bps, N/8/1, function codes 0x03 (read holding registers) and 0x06 (write single register); host timeout 10 seconds or more.

Data pointDescriptionTypical use
H₂ instantaneousCurrent dissolved hydrogen value, 1 ppm resolutionLive display, alarm logic
H₂ average / hourly averageRolling averages to damp out oil-circulation noiseTrend charts, gas-rate calculation
Rate of changeDaily, weekly and monthly trend gradientsEarly fault detection before absolute thresholds are crossed
Oil temperature−40 ~ +120 ℃, ±1 ℃Temperature-compensated trending
Moisture (%RS)Optional channel, 0–100 %RSPaper ageing, bubble evolution risk
Oil pressureOptional channel, 0–1 MPaSeal and breathing assessment
Device status bitsFault, calibration state, range overflowSupervision from your own SCADA
Relay statusAlarm relay state (via controller on the integrated version)Interlock and annunciation
Model and serial numberRead-only identificationFleet inventory, warranty tracking

The register map and integration document are supplied under NDA — we do not publish register addresses on an open page. Calibration is corrected over the serial command interface (DA / DB / DX) against an off-line ASTM D3612 oil analysis; if a reading deviates by more than 15 %, the sensor is corrected to the laboratory value.

OEM Options

The same sensing platform is available at three levels of completion. Choose the level that matches how much of the product you build yourself.

OptionChoicesWhat it changes
Completion levelDGA-300 element / DGA-500 standalone sensor / DGA-200 integrated instrumentHow much enclosure, power, relay and firmware you supply
Sensing principleDGA-300: palladium-alloy MOSFET structure, 2–2 000 ppm, oil 0 ~ +60 ℃, 350 g
DGA-500: palladium-alloy thin-film resistor, 5–5 000 ppm, oil −40 ~ +105 ℃, 500 g
Detection limit, range and oil temperature window
Measuring channelsH₂ only · + moisture (0–100 %RS) · + oil pressure (0–1 MPa)Number of Modbus data points and price
OutputRS-485 Modbus RTU · 4–20 mA and 3× alarm relays via the DGA-200 controllerWhether your host speaks Modbus or analogue
Process connection1/2 in. two-ferrule tube fitting; ferrule-to-flange adapter for ball-valve mountingRetrofit against existing valve sizes
CableLength and termination per orderRouting distance to the marshalling box
BrandingNeutral / your label / our labelWhether the unit ships as your product
DocumentationDatasheet · register map and integration guide (NDA) · factory inspection report · certificate of conformityWhat your engineering team receives before first article

Full OEM terms, including private label and regional exclusivity, are on the OEM sensor page and the partnership page.

MOQ, Lead Time and Volume Tiers

We quote against three tiers rather than publishing a single minimum, because the element, cable, channel options and branding all move the unit cost.

TierPurposeWhat is quoted
Evaluation sampleFirst article on your bench — Modbus polling, oil immersion, firmware integrationUnit price, packing, freight; documentary support during evaluation
Pilot batchField trial on customer transformers before committing to a product lineTiered unit price, confirmed production lead time, firmware/register support
Annual volumeSeries supply under your brandVolume price, scheduled deliveries, private label, regional exclusivity eligibility

Minimum quantities and lead-time weeks for each tier are confirmed at quotation against the specific configuration — sample and production quantities are always quoted separately. Warranty is 24 months from shipment on DGA-300 and DGA-500, extendable by agreement.

Not sure which tier fits? Send the target quantity and the transformer population you are addressing — we will tell you which tier applies before you commit.