Overview
A dissolved-hydrogen sensor that mounts independently on the transformer body, installed directly at the transformer ball valve and suitable for outdoor service. IP67 protection together with an applicable oil temperature of −40 ~ 105 ℃ allows long-term operation in outdoor transformer environments. The chip uses a palladium alloy thin-film resistor structure with a mature, stable Pd-alloy doping system, giving excellent long-term stability and freedom from periodic maintenance. In addition to dissolved hydrogen and oil temperature, the DGA-500 can be supplied with an optional moisture sensor and an optional oil pressure sensor.
Mounts directly at the transformer ball valve — IP67, −40 ~ 105 ℃ applicable oil temperature
Key Features
Solid-State Palladium Alloy Thin-Film
The chip uses a palladium alloy thin-film resistor structure with a mature, stable Pd-alloy doping system and specific composite thin-film fabrication, giving excellent long-term stability and sensitivity with no oil-gas separation.
Hydrogen-Specific Coating
A specific coating lets the sensor work reliably in backgrounds containing CO and CH compounds, so detection accuracy is not affected by other gases.
Hydrogen Detection in Different Backgrounds
Supports on-line hydrogen monitoring in mixed-gas backgrounds such as N₂, pure O₂ and inert gases.
Self-Regulating Working Temperature
A thin-film temperature sensor is integrated on the chip, allowing the working temperature to be adjusted automatically — no external temperature or flow-control devices are required.
Optional Moisture and Oil Pressure
Add a moisture sensor (0 ~ 100 %RS) and an oil pressure sensor (0 ~ 1 MPa) to the dissolved hydrogen and oil temperature measurement.
IP67, Outdoor Capable
IP67 protection with a −40 ~ 105 ℃ applicable oil temperature for long-term outdoor service. A corrosion-proof enclosure is available as an option for harsher site conditions.
Digital and 4 ~ 20 mA Analog Outputs
RS-485 with Modbus_RTU for configuration and data, plus an isolated 4 ~ 20 mA analog output whose span is configurable to the reporting range — so the DGA-500 can drive a SCADA or PLC analog input directly.
Technical Specifications
Dissolved Hydrogen
| Detection Principle | Palladium alloy thin film |
| Measuring Range | 5 ~ 5000 ppm |
| Limit of Detection | 5 ppm |
| Accuracy | ±15% reading or ±5 ppm (whichever is greater) |
| Repeatability | ±5% reading or ±5 ppm (whichever is greater) |
| Resolution | 1 ppm |
| Applicable Oil Temperature | −40 ~ 105 ℃ |
| Response Time τ90 | < 30 min (oil concentration above 100 ppm) |
Moisture (optional)
| Measuring Range | 0 ~ 100 %RS |
| Accuracy at 20 ℃ | 0 ~ 90 %RS: ±2 %RS 90 ~ 100 %RS: ±3 %RS |
| Response Time τ90 | < 10 min |
Oil Temperature
| Measuring Range | −40 ~ 120 ℃ |
| Accuracy at 20 ℃ | ±1 ℃ |
Oil Pressure (optional)
| Measuring Range | 0 ~ 1 MPa |
| Accuracy | ±1 % F.S. |
| Resolution | 0.1 kPa |
| Overload Capacity | 3 MPa |
Electrical & Other
| Power Supply | 24 V DC ±10%, 0.3 A (max) |
| Digital Output | RS-485 |
| Communication Protocol | Modbus_RTU |
| Analog Output | Isolated 4 ~ 20 mA, span configurable (fault 3.5 mA, not-ready 2.0 mA) |
| Ingress Protection | IP67 |
| Data Storage | Default interval 30 s (adjustable), 74,604 entries |
| Expected Life | 10 years |
| Weight | ≤ 500 g |
Type Configurations
| DGA-500 Base | Dissolved hydrogen and oil temperature sensor |
| DGA-500 with moisture | Plus moisture sensor |
| DGA-500 with moisture and oil pressure | Plus moisture and oil pressure sensors |
| Corrosion-proof enclosure | Optional, for DGA-500 |
Outline Dimensions
| Body Length | 226 mm |
| Probe Rod Length | 110 mm |
| Overall Length | 241.5 mm |
| Probe Rod Diameter | φ12.7 mm |
| Probe Root to Fitting | ≤ 45 mm |
| Process Connection | 1/2 in. two-ferrule tube fittings |
Range Limit
Range limit: the DGA-500 may only be used for hydrogen measurement in oil below 5000 ppm. Exceeding this range may cause the sensor chip to drift or even fail. Operation beyond the measuring range may cause irreversible damage to the sensor probe. A corrosion-proof enclosure is available as an option for this product.
Calibration follows the product manual: save the current state with the DA command, take an oil sample near the probe for off-line DGA analysis per ASTM D3612, and if the deviation exceeds 15% calibrate to the actual value with the DB command. The DX command clears the calibration data and returns the unit to factory calibration. Oil temperature, pressure and moisture calibration is performed with the CT command over RS-232 or via the MODBUS_RTU protocol.
Model Comparison
| Feature | DGA-300 (OEM) | DGA-500 (Standalone) | DGA-200 (Integrated) | DGM-900 (Multi-Gas) |
|---|---|---|---|---|
| H₂ Range | 2 ~ 2000 ppm | 5 ~ 5000 ppm | 5 ~ 5000 ppm | — |
| H₂ Detection Limit | 2 ppm | 5 ppm | Not specified | — |
| H₂ Accuracy | ±20% or ±2 ppm | ±15% or ±5 ppm | ±15% or ±5 ppm | — |
| Applicable Oil Temperature | 0 ~ 60 ℃ | −40 ~ 105 ℃ | −40 ~ 105 ℃ | — |
| Multi-Gas | — | — | — | 7 gases + moisture O₂ / N₂ optional |
| Sensor Technology | Pd alloy MOSFET thin film | Pd alloy thin-film resistor | Palladium alloy thin film | Pd Thin-Film + LPAS |
| MODBUS | ✓ | ✓ | ✓ | ✓ |
| IEC 61850 | — | — | — | ✓ |
| Rating | IP67 | IP67 | IP66 | — |
| Weight | ≤ 350 g | ≤ 500 g | approx. 1.75 kg | — |
| Best For | OEM Integration | Standalone Transformer Mounting | Distribution Transformer Fleets | Critical Asset Protection |
The DGM-900 column repeats the figures already published on the DGM-900 product page and was not revised here; “—” marks a row not compared on this page. See the DGM-900 product page for its full specification.
Modbus Interface — Data Available to Your Host
DGA-300 and DGA-500 are standard hardware half-duplex Modbus RTU slaves. Default 19200 bps, N/8/1, function codes 0x03 (read holding registers) and 0x06 (write single register); host timeout 10 seconds or more.
| Data point | Description | Typical use |
|---|---|---|
| H₂ instantaneous | Current dissolved hydrogen value, 1 ppm resolution | Live display, alarm logic |
| H₂ average / hourly average | Rolling averages to damp out oil-circulation noise | Trend charts, gas-rate calculation |
| Rate of change | Daily, weekly and monthly trend gradients | Early fault detection before absolute thresholds are crossed |
| Oil temperature | −40 ~ +120 ℃, ±1 ℃ | Temperature-compensated trending |
| Moisture (%RS) | Optional channel, 0–100 %RS | Paper ageing, bubble evolution risk |
| Oil pressure | Optional channel, 0–1 MPa | Seal and breathing assessment |
| Device status bits | Fault, calibration state, range overflow | Supervision from your own SCADA |
| Relay status | Alarm relay state (via controller on the integrated version) | Interlock and annunciation |
| Model and serial number | Read-only identification | Fleet inventory, warranty tracking |
The register map and integration document are supplied under NDA — we do not publish register addresses on an open page. Calibration is corrected over the serial command interface (DA / DB / DX) against an off-line ASTM D3612 oil analysis; if a reading deviates by more than 15 %, the sensor is corrected to the laboratory value.
OEM Options
The same sensing platform is available at three levels of completion. Choose the level that matches how much of the product you build yourself.
| Option | Choices | What it changes |
|---|---|---|
| Completion level | DGA-300 element / DGA-500 standalone sensor / DGA-200 integrated instrument | How much enclosure, power, relay and firmware you supply |
| Sensing principle | DGA-300: palladium-alloy MOSFET structure, 2–2 000 ppm, oil 0 ~ +60 ℃, 350 g DGA-500: palladium-alloy thin-film resistor, 5–5 000 ppm, oil −40 ~ +105 ℃, 500 g | Detection limit, range and oil temperature window |
| Measuring channels | H₂ only · + moisture (0–100 %RS) · + oil pressure (0–1 MPa) | Number of Modbus data points and price |
| Output | RS-485 Modbus RTU · 4–20 mA and 3× alarm relays via the DGA-200 controller | Whether your host speaks Modbus or analogue |
| Process connection | 1/2 in. two-ferrule tube fitting; ferrule-to-flange adapter for ball-valve mounting | Retrofit against existing valve sizes |
| Cable | Length and termination per order | Routing distance to the marshalling box |
| Branding | Neutral / your label / our label | Whether the unit ships as your product |
| Documentation | Datasheet · register map and integration guide (NDA) · factory inspection report · certificate of conformity | What your engineering team receives before first article |
Full OEM terms, including private label and regional exclusivity, are on the OEM sensor page and the partnership page.
MOQ, Lead Time and Volume Tiers
We quote against three tiers rather than publishing a single minimum, because the element, cable, channel options and branding all move the unit cost.
| Tier | Purpose | What is quoted |
|---|---|---|
| Evaluation sample | First article on your bench — Modbus polling, oil immersion, firmware integration | Unit price, packing, freight; documentary support during evaluation |
| Pilot batch | Field trial on customer transformers before committing to a product line | Tiered unit price, confirmed production lead time, firmware/register support |
| Annual volume | Series supply under your brand | Volume price, scheduled deliveries, private label, regional exclusivity eligibility |
Minimum quantities and lead-time weeks for each tier are confirmed at quotation against the specific configuration — sample and production quantities are always quoted separately. Warranty is 24 months from shipment on DGA-300 and DGA-500, extendable by agreement.
Not sure which tier fits? Send the target quantity and the transformer population you are addressing — we will tell you which tier applies before you commit.