Enter the seven dissolved fault gases in ppm (µL/L). Leave any gas blank if it was not reported — each diagnostic panel activates automatically once the gases it needs are present. All calculations run in your browser; nothing is uploaded until you choose to email a report.
Gas concentrations (ppm)
Presets fill a representative gas pattern for each Duval zone. They are teaching examples, not field measurements.
Copy share linkDuval Triangle 1
Duval Triangle 1 — IEC 60599 Annex B
Duval Triangle 1
IEC 60599 Annex B
IEC basic gas ratios
IEC 60599 Table 1
Rogers four-ratio method
IEEE / Rogers ratio codes
IEEE C57.104-2019 status
Table 1 (90th percentile), age band 1–9 years
Need this result checked by an engineer?
Send yourself the full DGA report, or ask a PAS DGA engineer to review the gas pattern against IEC 60599 and your transformer history.
Download or email a report
Download PDF gives a one-page summary: input values with source labels, the four key results and the Duval plot. Email me the PDF report gives the detailed multi-page report with the ratio tables, the IEEE per-gas comparison, method coverage, references and the full disclaimer. The four checkboxes below apply to the emailed detailed report.
One-page summary edition. For the full report with all tables and references, use the email option below.
Please note: the detailed report is sent as a PDF attachment, which some mail servers may treat as spam. If it has not arrived within a few minutes, please check your spam or junk folder and mark it as “Not spam”.
Frequently asked questions
Which gases does Duval Triangle 1 use?
Only methane (CH₄), ethylene (C₂H₄) and acetylene (C₂H₂). The three concentrations are normalised to 100 percent before the point is plotted, so hydrogen, ethane, CO and CO₂ do not change the zone.
Which standards does the calculator apply?
Duval Triangle 1 follows IEC 60599 Annex B. The basic gas ratios follow IEC 60599 Table 1 and use five gases. Rogers codes follow the classical four-ratio method. The IEEE status panel uses C57.104-2019 Table 1 for the 1 to 9 year age band; Table 2 is not reproduced.
Are the preset values real measurements?
No. Presets are teaching examples chosen to land in a specific Duval zone. Every report labels each value as Entered, Preset, From link or Not provided, and the PDF warns when preset values are used.
What is the difference between the downloaded and emailed report?
The download is a one-page summary with the inputs, source labels, key results and the Duval plot. The emailed report is the detailed multi-page version with the ratio tables, the IEEE per-gas comparison, method coverage, references and the full disclaimer.
Can the tool replace a laboratory oil test?
No. Results are generated by applying published rules mechanically. A final diagnosis needs a laboratory oil test, gas generation rates and a qualified engineer who knows the transformer design and operating history.
Standards and scope. Duval Triangle 1 follows IEC 60599 Annex B. The basic gas ratio diagnosis follows IEC 60599 Table 1. Rogers ratio codes follow the classical Rogers / IEEE ratio method. The IEEE C57.104-2019 status panel uses only the Table 1 90th-percentile boundary for the 1–9 year age band and the selected O₂/N₂ ratio; it does not reproduce the Table 2 boundary, so a reading above Table 1 is reported as a Status 2/3 candidate rather than a final status.
Disclaimer. Results are generated by mechanically applying published ratio and zone rules. They are for reference only. A final diagnosis must be confirmed by a laboratory oil test, a review of gas generation rates, and a qualified engineer who knows the transformer design, loading history and operating conditions.
Tool version: IEC 60599:2022 · GB/T 7252 · IEEE C57.104-2019 · PAS DGA web tool v2.0