When the IEC published the fourth edition of its partial-discharge standard in June 2025, it also changed the title: IEC 60270 is now Charge-based measurement of partial discharges. The rename marks out what the standard does and does not cover. It governs conventional, charge-based measurement of partial discharge (PD) — the calibrated picocoulomb reading taken in a laboratory or during an offline test. Everything an online monitor does at a substation, from UHF to acoustic sensing, follows a different track. Reading the PD standards map correctly is what keeps a specification defensible.

Two families of PD measurement

Partial discharge is a small breakdown that does not bridge the insulation, radiating energy across a wide spectrum — charge at low frequency, electromagnetic waves in the UHF range, sound in the acoustic range. Conventional measurement listens to the charge through a coupling capacitor and reports apparent charge in picocoulombs (pC); non-conventional measurement listens to UHF, high-frequency current-transformer (HFCT) or acoustic signals and reports in decibels or millivolts. The two families answer the same question in different units, and sit under different standards.

What IEC 60270 defines, and what IEC TS 62478 adds

The standard specifies the measurement circuit, the calibration procedure and the expression of results for charge-based PD measurement, including the apparent-charge value in pC and the role of a calibrator injected at the test object. It is the reference for offline and laboratory measurement, and its fourth edition (2025) restates the method while pointing the high-frequency band toward IEC TS 62478. The value of such a standard is comparability: a pC figure means something only when circuit, calibration and bandwidth are defined.

For in-service measurement, IEC TS 62478 covers the non-conventional UHF, HFCT and acoustic methods. These do not produce a calibrated pC value and instead rely on pattern recognition and trending; GB/T 42287 is the Chinese implementation of the same specification. A device positioned against this standard should describe its capability as designed in line with IEC TS 62478 (and DL/T 1498.1 for the device itself) — a statement of method, not a certificate. That distinction matters in a tender: “designed to” describes the approach a product adopts, while a type test is separate evidence.

Why a pC value does not travel

Apparent charge is defined only within a particular measurement circuit and calibration. An offline pC reading from a coupling capacitor cannot be transferred to an online UHF monitor, because the UHF channel measures a different physical quantity, and there is no honest conversion factor between them. This is the most common source of confusion in PD specifications, and why online specifications should use deviation from a self-established baseline rather than a threshold copied from a pC number. A UHF or HFCT channel can still support location by time-of-arrival, but “assisted location” is the accurate phrasing, not guaranteed triangulation.

The device and application standards

Standard Governs Unit / output
IEC 60270:2025 (Ed. 4) Conventional, charge-based PD measurement (offline / lab) Apparent charge, pC
IEC TS 62478:2016 Non-conventional online PD: UHF, HFCT, acoustic dB / mV, pattern-based
GB/T 42287 Chinese implementation of IEC TS 62478 dB / mV, pattern-based
DL/T 1498.1 General requirements for online monitoring devices Device-level
IEEE C57.127-2018 Acoustic PD detection only Acoustic
IEEE C57.113-2023 PD measurement guide Reference

Note the scope limits. IEEE C57.127 covers acoustic detection and cannot support a UHF or HFCT source. DL/T 1498.1 addresses the device rather than the measurement physics, so it belongs alongside, not instead of, the measurement standard.

Is online PD monitoring “IEC 60270 compliant”?

Not in the calibrated-pC sense. Online non-conventional PD is governed by IEC TS 62478; the charge-based method above is the conventional one used offline and in the laboratory. Asking an online UHF channel for a pC figure is asking for a number that channel cannot produce.

Can I compare an offline pC reading with an online dB reading?

No. They measure different physical quantities and there is no valid conversion between them. Trending each channel against its own baseline is the sound approach.

Positioning an online PD system against the map

PAS DGA’s TPD-400 online partial discharge monitor is designed in line with IEC TS 62478 and GB/T 42287 for non-conventional PD measurement, with IEC 61850 (DL/T 860) and DL/T 1498.1 for the device layer, and combines UHF, HFCT, acoustic and RF inputs in one unit (vendor data). Measuring online activity in dB and mV rather than calibrated pC, it complements conventional testing rather than replacing it — the pairing we set out in partial discharge versus dissolved gas analysis. Together with the DGM-900 multi-gas monitor it forms a two-axis condition picture: DGA reads the chemical consequence of a fault, online partial discharge monitoring system reads its electrical activity while it is present. Requirements are summarised on our standards page, and the background in online partial discharge monitoring to IEC TS 62478. Send a PD specification through the contact page and we will map it against the standards above.

Sources: IEC 60270:2025 (Ed. 4); IEC TS 62478:2016; GB/T 42287; DL/T 1498.1; IEEE Std C57.127-2018 (acoustic detection only); IEEE Std C57.113-2023. TPD-400 channel specifications are vendor data.