September 9, 2026 · Fault Diagnosis

A 2026 CIGRE D1 paper describes online radiometric partial-discharge monitoring across high-voltage air-insulated substation assets; in one 245 kV capacitor-voltage-transformer case it confirmed discharge activity above 300 pC in service, well before a scheduled inspection would have caught it. The same reasoning now reaches inside the transformer tank: online partial discharge monitoring for transformers is becoming a standard line in condition-monitoring RFQs.

What online partial discharge monitoring measures

Partial discharge (PD) is localized electrical breakdown inside insulation that has not yet bridged the gap between conductors. In a transformer it appears as corona, surface discharge, or discharge in gas-filled voids of the paper-oil insulation. Each pulse lasts nanoseconds to microseconds and carries an apparent charge measured in picocoulombs (pC); the pulses repeat in phase with the AC cycle. Plotted phase-resolved, as a PRPD or PRPS pattern, they let an engineer tell a void discharge from surface tracking or corona, and let software classify the pattern automatically. Because PD erodes paper and oil until it becomes tracking, carbonization, and finally a dielectric failure, catching the progression early is the purpose of a continuous monitor.

Four sensing methods, one picture

No single sensor sees every discharge site, so online systems combine sensing methods. The four used on transformers are compared below.

Method Sensor location Typical band What it catches
UHF Inside the tank via oil-valve or manhole port 300–1500 MHz Internal discharges with low noise pickup; supports time-difference localization
HFCT Clamp around grounding, neutral, or bushing-tap conductors 0.3–30 MHz Discharge current pulses on connected metallic paths
AE (acoustic) On the external tank wall 80–200 kHz Ultrasonic pressure waves from discharges; useful for localization
RF (radiometric) Near the asset, antenna-based Broadband Electromagnetic emissions; also used for switchyard assets

Band figures are typical manufacturer values (vendor data). The framework for these online, non-conventional methods is IEC TS 62478 and its Chinese equivalent GB/T 42287; laboratory measurement follows IEC 60270. One pitfall: IEEE C57.127 covers acoustic methods only, so it does not justify a UHF or HFCT deployment.

What to look for in a monitoring system

A practical system ties the sensors to a single acquisition unit. When you compare options for online partial discharge monitoring for transformers, start on the acquisition side: synchronous multi-channel sampling in the 100 MS/s class at 12–14 bit, so pulses across sensors can be compared with inter-channel timing skew below 100 ns — the basis for source localization. On the analysis side, look for PRPD/PRPS visualization plus an automatic pattern-recognition engine that classifies discharge type and tracks severity, rather than raw waveforms an engineer must interpret by hand.

Designed in line with those requirements, the TPD-400 online PD monitoring system takes UHF, RF, acoustic, and HFCT inputs into one industrial IED with synchronized acquisition (125 MS/s, 14-bit, vendor data), 2D and 3D phase-resolved plots, and a neural-network pattern-classification engine. Compliance wording matters too: reputable vendors state their equipment is designed in line with IEC TS 62478 and GB/T 42287 for non-conventional online PD measurement, IEC 61850 (DL/T 860) for station communication, and DL/T 1498.1 for online monitoring devices — type-test claims should always be checked against an actual report. A short specification checklist:

  • Sensor inputs: UHF (oil-valve/manhole) plus HFCT in one IED, acoustic or RF as options.
  • Digitizer: synchronized channels, ~100 MS/s or higher, ≥12-bit, inter-channel sync in tens of nanoseconds.
  • Sensitivity: a usable floor in the single-digit pC range (TPD-400 quotes ~5 pC, vendor data) and a stable baseline so trends stay meaningful.
  • Diagnostics: PRPD/PRPS plots with pattern recognition and trend-first alarm logic.
  • Integration: IEC 61850 (DL/T 860) and Modbus outputs so PD sits beside DGA and load data.

Can PD monitoring be retrofitted without an outage?

Usually yes, and retrofit drives much of the market. A UHF sensor fits through an existing oil drain or sampling valve, and an HFCT clamps around a grounding conductor, so both can be installed on an energized transformer where the site safety procedure allows. For 110 kV and above, Chinese guidance T/CSEE 0421 addresses oil-valve UHF installation and is a useful reference when planning a live retrofit.

Does PD monitoring replace DGA?

No — dissolved gas analysis (DGA) remains the best single indicator of overall fault development, and a dissolved hydrogen sensor is the most economical fleet-wide early warning. PD adds what oil cannot: confirmation that an electrical discharge is active right now, its phase-resolved signature, and a location when multiple sensors are fitted. The practical relationship between the two is laid out in our PD vs DGA comparison; the usual program is DGA or hydrogen across the fleet plus online partial discharge monitoring for transformers on critical units — generator step-ups, interties, and stations with limited redundancy.

Build a transformer condition monitoring program

PAS DGA builds both halves of the picture. The TPD-400 covers the partial-discharge side; the DGA-900 nine-gas monitor and the hydrogen sensor range cover dissolved gas, so one supplier can instrument a transformer for full insulation-condition visibility. Start with the compliance-oriented hydrogen baseline, then add a PD channel where electrical risk is highest.

Talk to us about specifying an online partial discharge monitoring system for your transformers.