November 13, 2026 · DGA Technology

A gas-in-oil reference standard is the only sample that tests a dissolved gas analysis (DGA) measurement chain from end to end: the same oil, the same extraction, the same detector, with a concentration stated in advance. Everything a monitor reports afterwards is compared, directly or indirectly, to a sample like this. The arithmetic of making one is simple. The physics of getting the gas into the oil is where the uncertainty lives.

Two preparation routes in IEC 60567

IEC 60567:2023, Clause 7, describes two ways to prepare gas-in-oil standards. The large-volume method uses a 5 L vessel, a 6 L oil reservoir and a mercury displacement system. The vessel is evacuated and oil is admitted slowly, with a filling time of about four hours intended to leave the oil virtually gas-free. Gases are then injected through a septum with gas-tight syringes. The second method prepares standards directly in a syringe or a vial. It is simpler and smaller, at the cost of a smaller batch and tighter handling limits.

Both routes end in the same place: a known amount of gas dissolved in a known volume of oil. The difference between a reference that supports a ±5% judgement and one that only supports a ±15% check is not the glassware. It is how carefully mass, volume, temperature and transfer are accounted for.

From mass to microlitres per litre

The large-volume method is gravimetric because the oil is weighed rather than poured to a mark. The sequence is direct:

  1. Weigh the empty vessel, fill with degassed oil, weigh again. The difference m₁ − m₀ is the oil mass.
  2. Divide by density measured at 20 °C: V = m / ρ. A densitometer contributes far less error than a meniscus read with 0.1–0.5% volumetric error on a 5 L vessel.
  3. Inject each component through the septum below the oil surface. The syringe volume is corrected to 20 °C and 101.325 kPa: Vᵢ = Vread × (p / 101.325) × (293.15 / (273.15 + t)).
  4. Stir for at least four hours, long enough for the gas to dissolve and the batch to homogenise.
  5. Calculate C = Σ(xᵢVᵢ) / Voil × 10⁶, in µL/L at 20 °C and 101.325 kPa.
Quantity How it is fixed Typical relative uncertainty Traceability
Oil mass Balance, m₁ − m₀ 0.02–0.1% kilogram
Oil volume Mass ÷ density at 20 °C 0.1–0.2% kg/m³
Injected gas volume Syringe, pressure and temperature corrected 0.5–1% m³, K, Pa
Gas amount fraction Certified mixture 1–2% mole
Dissolution and transfer Procedure, not measured 1–5% —

No partition coefficient appears anywhere in that chain. That is the method’s real advantage over preparing oil by calculation from Ostwald coefficients, where tabulated values for the same gas in the same oil can differ by tens of per cent between sources.

What the certificate can and cannot claim

Gravimetric preparation of gas mixtures is a primary method. ISO 6142-1:2015 defines Class I mixtures whose values are traceable to the kilogram and the mole through weighing, with expanded uncertainties around 1% at k = 2 demonstrated in published comparisons. That is the preparation step. A delivered gas-in-oil reference standard is a different quantity.

Commercial gas-in-oil standards are produced under ISO 17034 and certified with a stated uncertainty that includes a verification analysis; one widely used product line specifies 5% or 2 ppm, whichever is greater (vendor data). The gap between 1% preparation and 5% certification is not sloppiness. It is what happens between preparation and use: homogeneity, ampoule-to-ampoule variation, storage, and the verification method itself.

For a monitor judgement at ±5%, a reference at 5% already sits at the edge of the half-window rule. That is the subject of the next article in this series.

Is a gravimetric gas-in-oil standard traceable to SI units?

Yes, through two paths: mass to the kilogram via the balance and the certified gas mixture, and amount of substance to the mole via the gas certificate. Density and syringe volume are intermediate quantities, themselves calibrated. The chain has no empirical constant that must be taken on trust, which is why metrology laboratories prefer it for reference materials.

Can the syringe method replace the large-volume method?

For a quick check of extraction efficiency, yes. For a certification-grade batch, the large-volume method remains the reference: a 5 L batch averages out local inhomogeneity that a 100 mL syringe cannot, and it gives enough aliquots for repeatability and stability tests. The syringe method is a working tool; the large-volume method is the anchor.

PAS DGA builds monitors for the whole chain, from the dissolved hydrogen sensor to the DGM-900 seven-gas analyzer. If you are qualifying a reference standard or comparing a field reading with a laboratory value, contact our team. For the rest of the measurement chain, start with laboratory gas standards for DGA, or read how headspace, vacuum and membrane degassing shape what a monitor sees.

Sources
IEC 60567:2023, Clause 7 — preparation of gas-in-oil standards. ISO 6142-1:2015 — gravimetric preparation of calibration gas mixtures, Class I. ISO 17034:2016 — general requirements for reference material producers. Doble Engineering, “Laboratory Accreditation: Accuracy and Precision” (laboratory guidance). Morgan Schaffer, True North gas-in-oil standard, technical specification (vendor data). CIGRE Technical Brochure 409, Report on Gas-filled Monitors.