Duval Triangle 1 — Interactive DGA Calculator

Enter dissolved gas concentrations in ppm. The calculator normalizes CH₄, C₂H₄, and C₂H₂ to percentages and plots the result on the Duval Triangle with automatic fault diagnosis.

Gas Concentrations (ppm)

Duval Triangle 1 — IEC 60599 Annex B

Fault Zone Reference

Zone Fault Type Temperature / Energy Action
PD Partial Discharge Low energy Monitor & trend. Investigate if increasing.
T1 Thermal fault < 300°C Low temperature Schedule inspection. Check for overload.
T2 Thermal fault 300-700°C Medium temperature Plan outage. Loose connection likely.
T3 Thermal fault > 700°C High temperature Urgent. Carbonized paper risk.
D1 Low-energy discharge Spark / tracking Investigate within 1 month.
D2 High-energy discharge Arcing — extreme IMMEDIATE shutdown. Major failure risk.
DT Mixed thermal + electrical Combined fault Investigate. May be fault in transition.